Ex e mb II, Ex tD A21 Maintenance Free Fluorescent Luminaire
TNAML
Features
• 10 year operational warranty gives low lifecycle cost*
• 100% encapsulated.
• Maintenance free solution requiring only visual inspection to IEN/EN 60079-17
• Easy and flexible installation
• Seawater resistant anodized aluminum
• Tempered glass
• Fully recyclable
• High light efficiency (80%)
• Available with 2x18W / 2x36W / 2x58W lamps
• Optional integrated battery powered LED emergency lighting
• Sealed-for-life concept
• Fit and forget
• Patented design
• Vibration test:
Standard: IEC60721-2-3 Ed 1.0 and IEC68-2-6
Frequency range: 1 - 150 Hz
Amplitude: 5mm (1 to 10 Hz)
Acceleration: 2 gn (10 to 150 Hz)
Sweep rate: 1 octave per minute
# sweep cycles: 10
# directions:
General specifications:
Modes of protection Ex e mb, Ex tD A21
ATEX classification Group II Category 2 G D
Zones 1, 2, 21, 22
Applied standards EN/IEC: 60079-0, 60079-7, 60079-18
EN: 61241-0, 61241-1
Approvals
- Atex KEMA 08ATEX0163
Ex code II 2 G Ex e mb II T6
II 2 D Ex tD A21 IP66 T80°C
Inspection Visual inspection in accordance with EN/IEC 60079-17
Product specifications:
Housing Seawater resistant anodized (25 micron) aluminium with tempered glass
Lamps Pre-mounted long life T8 lamps, colour temperature 4000K
IP Rating IP66
Temperature range -20°C to +55°C
Voltage 220-264VAC 50/60Hz
Electrical connection 0.5-6mm2 spring terminals through integrated external junction box (sealed by resin)
Entries 2 x Ø25 mm cable gland entries. One plugged.
Ballast Electronic with end of life protection
Mounting 2 x adjustable brackets on guidance rail for easy and quick installation
LED Emergency lighting 90 minute battery backup
Options (upon request, minimum quantities may apply):
Voltage 110/120VAC, 50/60 Hz (only for 2x18W and 2x36W)
Lamps Colour temperature 3000K
Electrical connection 8 metre permanent flying lead, braided
LED Emergency lighting 180 minute battery back-up
4 LEDs to meet requirements of IMO/DNV-OS-A101
Glass For use in accordance with HACCP environment
Wiring 1 junction box at each side for through wiring, max. 2,5 sqmm
Other area classifications Zone II, Ex n, 3 GD (TNAMLC...) or safe area version (TNAMLD...)
Accessories
Mounting brackets Pole and ceiling mounting brackets
Safety wire For installation into a fixing arrangement on the light fitting
Cable Gland Suitably rated cable glands can be supplied with the light fitting
Manned/Unmanned facilities Wireless “Black start” function for manned/unmanned functionality.
TNAML
• 10 year operational warranty gives low lifecycle cost*
• 100% encapsulated.
• Maintenance free solution requiring only visual inspection to IEN/EN 60079-17
• Easy and flexible installation
• Seawater resistant anodized aluminum
• Tempered glass
• Fully recyclable
• High light efficiency (80%)
• Available with 2x18W / 2x36W / 2x58W lamps
• Optional integrated battery powered LED emergency lighting
• Sealed-for-life concept
• Fit and forget
• Patented design
• Vibration test:
Standard: IEC60721-2-3 Ed 1.0 and IEC68-2-6
Frequency range: 1 - 150 Hz
Amplitude: 5mm (1 to 10 Hz)
Acceleration: 2 gn (10 to 150 Hz)
Sweep rate: 1 octave per minute
# sweep cycles: 10
# directions:
General specifications:
Modes of protection Ex e mb, Ex tD A21
ATEX classification Group II Category 2 G D
Zones 1, 2, 21, 22
Applied standards EN/IEC: 60079-0, 60079-7, 60079-18
EN: 61241-0, 61241-1
Approvals
- Atex KEMA 08ATEX0163
Ex code II 2 G Ex e mb II T6
II 2 D Ex tD A21 IP66 T80°C
Inspection Visual inspection in accordance with EN/IEC 60079-17
Product specifications:
Housing Seawater resistant anodized (25 micron) aluminium with tempered glass
Lamps Pre-mounted long life T8 lamps, colour temperature 4000K
IP Rating IP66
Temperature range -20°C to +55°C
Voltage 220-264VAC 50/60Hz
Electrical connection 0.5-6mm2 spring terminals through integrated external junction box (sealed by resin)
Entries 2 x Ø25 mm cable gland entries. One plugged.
Ballast Electronic with end of life protection
Mounting 2 x adjustable brackets on guidance rail for easy and quick installation
LED Emergency lighting 90 minute battery backup
Options (upon request, minimum quantities may apply):
Voltage 110/120VAC, 50/60 Hz (only for 2x18W and 2x36W)
Lamps Colour temperature 3000K
Electrical connection 8 metre permanent flying lead, braided
LED Emergency lighting 180 minute battery back-up
4 LEDs to meet requirements of IMO/DNV-OS-A101
Glass For use in accordance with HACCP environment
Wiring 1 junction box at each side for through wiring, max. 2,5 sqmm
Other area classifications Zone II, Ex n, 3 GD (TNAMLC...) or safe area version (TNAMLD...)
Accessories
Mounting brackets Pole and ceiling mounting brackets
Safety wire For installation into a fixing arrangement on the light fitting
Cable Gland Suitably rated cable glands can be supplied with the light fitting
Manned/Unmanned facilities Wireless “Black start” function for manned/unmanned functionality.